|
Limited
number of components means
fewer problems in three-phase motors
Three-phase motors
have fewer components that may malfunction than
other motor types. Therefore, three-phase motors
usually operate for many years without any problems.
If a three-phase
motor is the problem, the motor is serviced or
replaced. Servicing usually requires that the motor
be sent to a motor repair shop for rewinding. If the
motor is less than 1 HP and more than five years
old, it is replaced. If the motor is more than 1 HP,
but less than 5 HP, it may be serviced or replaced.
If the motor is more than 5 HP, it is usually
serviced.
Troubleshooting Three-Phase Motors
The extent of troubleshooting a three-phase motor is
dependent upon the motor's application. If the motor
is used in an application that is critical to the
operation or production, testing is usually limited
to checking the voltage at the motor. If the voltage
is present and correct, the motor is assumed to be
the problem.
Unless it is very large, the motor is usually
replaced at this time so production can be resumed.
If time is not a critical factor, further tests can
be made to determine the exact problem.

Figure 1 Troubleshoot three-phase motors with an
ohmmeter.
To troubleshoot a three-phase motor, apply the
following procedure:
1. Using a voltmeter, measure the voltage at the
motor terminals. If the voltage is present and at
the correct level on all three phases, the motor
must be checked. If the voltage is not present on
all three phases, the incoming power supply must be
checked.
2. If voltage is
present but the motor is not operating, turn the
handle of the safety switch or combination starter
OFF. Lock out and tag the starting mechanism per
company policy.
3. Disconnect the
motor from the load.
4. After the load
is disconnected, turn power ON to try restarting the
motor. If the motor starts, check the load.
5. If the motor does not start, turn it OFF and lock
out the power.
6. With an
ohmmeter, check the motor windings for any opens or
shorts. Take a resistance reading of the T1-T4 coil.
This coil must have a resistance reading. If the
reading is zero, the coil is shorted. If the reading
is infinity, the coil is opened. Since the coil
winding is made of wire only, the resistance is low.
However, there is resistance on a good coil winding.
The larger the motor, the smaller the resistance
reading.
After the resistance of one coil has been found, the
basic electrical laws of series and parallel
circuits are applied. When measuring the resistance
of two coils in series, the total resistance is
twice the resistance of one coil. When measuring the
resistance of two coils in parallel, the total
resistance is one half the resistance of one coil.
See Troubleshooting guides in additional three-phase
motor troubleshooting article below.
|